← voltar
CVE-2021-35533highCWE-20

Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series

21Vexday Risk Score

Sem sinal de exploração. Nenhum artefato público de exploração conhecido até agora.

ssvc Trackcvss 7.5epss 0.9%
probabilidade de exploração
0.9%top 43% das CVEs
exploração observada
nãonenhuma fonte reporta
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H